T44K | MITSUBISHI, S4S-DTSD MECC ALTE, ECO32-3S | - Mechanical governor
- Mechanically welded chassis with antivibration suspension
- Power circuit breaker
- Radiator for wiring T°of °C max with mechanical fan
- Protective grille for fan and rotating parts
- 9dB(A) silencer supplied separately
- Charged DC starting battery with electrolyte
- 12 V charging alternator and starter
- Supplied with oil and coolant -30°C
- User manual and commissioning guide
|
| | Voltage (V) | ESP power (kWe/kVA) | PRP power (kWe/kVA) | Back-up power (A) | Size (mm) | Weight | | 415/240 | 35.2 / 44.0 | 32.0 / 40.0 | 61 | | 400/230 | 35.2 / 44.0 | 32.0 / 40.0 | 63 | | 380/220 | 35.2 / 44.0 | 32.0 / 40.0 | 66 | | 240/120 | 35.2 / 44.0 | 32.0 / 40.0 | 105 | | 230/115 | 35.2 / 44.0 | 32.0 / 40.0 | 110 | | 220/110 | 35.2 / 44.0 | 32.0 / 40.0 | 115 | | 220/127 | 28.0 / 35.0 | 25.5 / 31.8 | 91 | | 200/115 | 35.2 / 44.0 | 32.0 / 40.0 | 127 | | | L: 1700 | 680 Kg Net | | W: 896 | 790 Kg Brut | | H:1223 | | | | | Model | dB(A) @1m | dB(A) @7m | Size (mm) | Weight | Tank |  | M127 | 71.1 | 61.1 | | Length : 2080 | | Width : 960 | | Height : 1415 | | | 100 L | Control Modules available: | | Standard | NEXYS |
|---|
| | | Specifications : Frequency meter, Ammeter, Voltmeter Alarms and faultsOil pressure, water temperature, Overcrank, Overspeed ( >60 kVA), Min/max alternator, Low fuel level, Emergency stop Engine parameters : Hours counter, Engine speed, Battery voltage, Fuel level, AIr preheating | |
| Option | TELYS |
|---|
| | | Specifications : Frequency meter, Ammeter, Voltmeter Alarms and faults : Oil pressure, water temperature, No start-up, Overspeed, Min/max alternator, Min/max battery voltage, Low fuel level, Emergency stop Engine parameters : Hours counter, Oil pressure, Water temperature, Engine speed, Battery voltage, Fuel level | |
|
|